Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

corgone

Unregistered

1

Wednesday, March 8th 2017, 11:54am

Running a main line under the driveway

In order to put multiple valves in the front of the house, I needed to run a 1.25 main from the back to the front going under the driveway. I started about 12-18" below ground on one side, but the pipe dropped and came out about 4' below ground on the other. Not what I was expecting.

Is there any problem re-routing that back to 12"-18" below the surface with a couple elbows?

The overall yard is flat. I'm working with 50PSI design pressure and 20gpm coming off a well.

Thks
Chris

Wet_Boots

Supreme Member

Posts: 5,133

Location: Metro NYC

2

Wednesday, March 8th 2017, 4:10pm

You might want to figure out a way to add a drain to the low point, if you are in a freezing climate. (hopefully you aren't)

corgone

Unregistered

3

Wednesday, March 8th 2017, 5:35pm

Re: Running a main line under the driveway

Cold not an issue - Florida..... just curious if there would be any PSI issues, backflow, etc.... Mostly it's an irritant to me because I know it.

Thks

Wet_Boots

Supreme Member

Posts: 5,133

Location: Metro NYC

4

Friday, March 10th 2017, 12:00pm

No issues over the extra pipe and fittings involved. The thing to remember here is that all fittings translate to a length of pipe a few feet long, when it comes to calculations of pressure losses.