Wednesday, June 13th 2018, 10:21am

Backflow pressure

Having some issues with water pressure in my system. I placed a pressure gauge on the first test cock on the backflow preventer and get a reading of 50PSI, as soon as i open a valve it drops down to 17/18PSI and stays there. Seems that is way to much of a drop? The run from the meter to the backflow device is only about 2 ft and i don't see any puddling of water so i'm not sure if it's a leak? Any comments would be appreciated.

Wet_Boots

Supreme Member

Posts: 5,259

Location: Metro NYC

2

Wednesday, June 13th 2018, 3:40pm

Look for a partially-closed valve in the supply chain.