Station won't stop

I have a Toro green keeper, and my 3rd station will not stop. I assume it is the solenoid, but not sure, and is there a specific selenium for the green keeper?

hi.todd

Supreme Member

Posts: 480

Location: Houston, Texas

2

Monday, June 6th 2016, 7:43pm

It could be the valve solenoid is loose.
It could be a manual bleed screw is loose on the valve.
Or worse case, trash in the valve causing the valve to stick open.
Maybe worst case is that it is the timer.

You should locate the valve in the field and get your hands on it.

Also you could disconnect the wire for the zone at the timer and see if the zone stops working.

That should rule out the timer.