1 zone not working

I have a Hunter X-Core system with a master valve and 7 zones, all zones operate properly except for zone 7, the only way that I can get zone 7 to work is by opening up the bleeder valve, when I close bleeder the zone shuts down. I have checked power, replaced valve, solenoid and cleared line of any known debris...any suggestions?

mrfixit

Moderator

Posts: 2,151

Location: USA

2

Saturday, April 30th 2016, 2:12pm

How did you check the power to valve 7?

Is there a spare wire you can use?

Maybe you installed the new valve backwards.

wagon35

New Member

3

Saturday, April 30th 2016, 2:43pm

I did check power to zone 7 with meter and it was ok, I moved power from zone 7 to zone 6 and zone 6 worked, I also tried moving the power from zone 6 to zone 7 and zone 7 still not working, I also removed valve and turned it around just in case I put it on backwards but still not working