Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

rcspeed

Starting Member

1

Thursday, August 25th 2011, 12:48pm

squealing/whining

I have a Hunter Pro-c controller with hunter pop up sprinkler heads on 2 zones. I have a 3rd zone that has drip lines run off of it. the house has a main control valve and the sprinkler system has a main control valve.
The 2 popup sprinkler zones work fine. However, the zone that has the drip lines has a terriblesqueal/whine in the house pipes down by the main valve. If I adjust the pressure in the main valve on the sprinkler system side, the squeal goes away. However, it has returned. I readjusted the pressure and the squeal disappeared. It then worked a few days and returned. When I adjust the pressure control in the valve, it does not seem to make the reading on the pressure meter move, so therefore the adjustment is small.
Any suggestions on how to make the squeal permanently go away?
thanks.

Wet_Boots

Supreme Member

Posts: 3,880

Location: Metro NYC

2

Thursday, August 25th 2011, 3:34pm

You need a pressure regulator on the drip line - high-pitched noises often indicate a nearly-closed valve