How to drain a backflow preventer when winterizing sprinklers

I am preparing to do a winter blow-out for my sprinkler system. I had a plumber install a Watts 007 Double check valve assembly, it is located outside the house.

I have a blow-out/drain port downstream from the backflow preventer (outside), as well as before the DCVA (inside) I have read that it is bad for the Doublecheck valve to blow air through it, and that the air compressor should be hooked up after it (so, outside in my case).

I have already cut off the water source to the sprinklers and drained the inside piping. After I do the blow-out, how do I go about draining the water from the 007 itself?

Thanks.

ldcxyz

New Member

Posts: 10

Location: Montana

2

Saturday, April 3rd 2010, 6:43pm

Hookup downline from your backflow preventer, shut off the ball valves on the backflow preventer, and then blow out your sprinkler system. When you have completed this, open both ball valves 1/2 way, and open both test cocks on the backflow to allow the backflow to drain.

Rate this thread
AUUSAUK Businessroller chainroller chain manufacturers Motorcycle ChainTransmission chain Converor chain AU手机铃声手机铃声免费下载qq分组益智游戏公司袜子批发袜子批发厂家袜子批发价格外贸袜子批发UK Company
239802 2827 418297 20913 506350 25353 338162 26285 288227 38584 538294 419171 234762 8435 117003 363468 539228 682823 462792 176556 375088 411372 749282 1298152 1407602 1758242 675452 206558 1915768 748080 1699203 1732439 1854112 1373936 269097 1668171 882446 1648068 394437 1718603 1725056 294818 513656 1974993 161591 71222 2339578 455093 1238261 1876983 1182759 1730596 2528584 1577423 1198131 50331 2253280 2556974 1833585 275767