One zone not working

The last zone of a Rain Bird 12 zone system stopped working recently. I replaced the solenoid and that didn't make any difference but I noticed that when I opened the bleeder screw on the valve the zone worked fine. Any help would be greatly appreciated. ?(

mrfixit

Moderator

Posts: 1,464

Location: USA

2

Wednesday, May 13th 2009, 7:50pm

diaphragm

If the controller is activating the solenoid but the valve isn't coming on it's probably the diaphragm. Could be a clogged port or the flow control could be turned off.