Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Attention: The last reply to this post was 479 days ago. The thread may already be out of date. Please consider creating a new thread.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 10 posts

Thursday, May 9th 2013, 11:48am

by Scott76

If you are going to keep the MP rotors on there, you need to put PRS heads under them. The heads flow as much water as you supply them with. I've dealt with this type of issue many times. If you want to keep the MP's go buy 12 Hunter pro sprays with PRS and install them instead of the basic prospray's.

If you goto www.hunterindustries.com and look at the MP Rotators you will see under the specifications tab that the recommend an output pressure of 40 PSI. They say list an option of installing them on Prospray 4" with PRS. The other option would be pressure control on the valve, but that won't solve the problem.

http://www.hunterindustries.com/irrigation-product/nozzles/mp-rotator

The heads at 40 psi will put out .79 GPM each at 180 degrees. That equates to 9.48 GPM for that zone. Under most conditions that should be sustainable.

Wednesday, May 8th 2013, 11:49pm

by Wet_Boots

You are just guessing and changing parts, and good luck with that. Try some pressure and flow measurements.

Wednesday, May 8th 2013, 10:21pm

by SLCmonster (Guest)

sprinklers

yes it is on City water, all other stations work fine, plus the other 2 stations within this manifold work fine too, I have dug the whole thing up looking for leaks b/c it worked fine last year, didnt find anything but still replaced it to 1 inch pipe coming off the manifold all the way. it had been 1 inch to the T...and down to 3/4" there on out to the heads...I had some regular rainbird 1800s on there last year and they worked fine. changed to the mp2000 which should take less GPM but have a better coverage spray than the basic rainbird head... could that be the problem?.

Wednesday, May 8th 2013, 8:51pm

by Scott76

Buy 12 hunter pro sprays with PRS and install the same nozzles on the new heads. The MP's are just like rotors and will flow much more than their charted flow if the extra pressure is there. I'm 99% sure hunter says to install them on PRS heads.

Wednesday, May 8th 2013, 5:19pm

by Wet_Boots

Is this on city water? Are there any trees located so that their roots might cause a blockage?

Wednesday, May 8th 2013, 3:23pm

by SLCmonster (Guest)

last picture try


Wednesday, May 8th 2013, 3:22pm

by SLCmonster (Guest)

[/img] trying anyways

Wednesday, May 8th 2013, 3:20pm

by SLCmonster (Guest)

this is a rough drawing

Wednesday, May 8th 2013, 3:19pm

by SLCmonster (Guest)

layout


Wednesday, May 8th 2013, 2:49pm

by SLCmonster (Guest)

sprinklers

the ones above the T are at a slightly higher elevation running about 30 feet total and the curve running south of the T is about 110feet