Dear visitor, welcome to SPRINKLER TALK FORUM - You Got Questions, We've Got Answers. If this is your first visit here, please read the Help. It explains how this page works. You must be registered before you can use all the page's features. Please use the registration form, to register here or read more information about the registration process. If you are already registered, please login here.

Attention: The last reply to this post was 485 days ago. The thread may already be out of date. Please consider creating a new thread.

Message information
Message
Settings
Automatically converts internet addresses into links by adding [url] and [/url] around them.
Smiley code in your message such as :) is automatically displayed as image.
You can use BBCode to format your message, if this option is enabled.
Security measure

Please enter the letters that are shown in the picture below (without spaces, and upper or lower case can be used).

The last 2 posts

Friday, May 3rd 2013, 7:04pm

by Wet_Boots

Could be the pump relay is presenting an overload to the controller.

Friday, May 3rd 2013, 4:07pm

by lakebum20

Imperial Valet 11 station controller

A friend that I am trying to help has an OLD imperial valet controller with an intake in the lake. when a zone is turned on the I get 24 volts on the common and m terminals, and in about 3-4 seconds the reset button trips. It does this on each zone. Can start the pump at the lake by pressing in the contacts on the pump. Worked fine when winterized. What would cause the reset button to trip? System is probably over 20 years old and probably has the brass valves.